WORK INSTRUCTION
DKI GENERAL WIRING PRACTICES
1.

Scope

This work instruction shall be applied in the Diamond Key International Workshops
Electrical wiring on skids or associated is required.

All wiring to be performed by qualified experienced wiring personnel using
appropriate tools for stripping insulation, cutting, soldering and attaching
mechanical crimp type terminals with the correct dies and tools as advised by the
terminal manufacturer.

Foremost electrical installations are to be performed to latest issue of wiring
rules AS/NZS 3000 as well as IEC directives

2.

General installation:

2.1.

When removing insulation from the conductor, wire strands shall not be
nicked or damaged. Proper stripping tools shall be used to avoid such damage.

2.2.

Wire and cable ties shall be snug but shall not be so tight as to
cause indentation and cold flow damage to the insulation.

2.3.

Cable ties shall be tensioned and trimmed using cable tie
manufacturers tooling.

(Use of side cutters for trimming, is not permitted)

2.4.

All wiring within Exe, Exi or similar enclosures to be terminated.

2.5.

Where possible, adhesive installed mounting bases should not be used
for ties or cable support unless affixed with a mechanical fastener.

2.6.

Wire and cable dress shall allow sufficient slack for removal and
reapplication of the wire terminations, at least twice without excess
tension.

2.7.

All wire and cable, including that in ducts and conduit, shall be
handled to be free from kinks and insulation abrasions.

2.8.

Wire installation shall not be subject to accumulation of water, oil
or other foreign matter.

2.9.

Instrument cables are to be free of Orange drain wires.

2.10.

Cable to be laid out neatly and undue crossing of cables is to be
avoided (refer Appendix 3).

2.11.

All wire shall be protected against any contact with any surface other
than that designed specifically to support or protect the wire.

2.12.

Protective edging, Grommets and similar materials shall be applied
wherever any possibility exists for a wire to contact a sharp edge.

2.13.

A drip loop shall be provided in each wire or cable where water could
otherwise run along the wire or cable to the point where it enters a box or
enclosure.

2.14.

Wire/cables forming part of the wiring system shall be bent in a
manner that will not cause damage or place undue stress on their sheathing or
insulation.

2.14.1.1.

Where
manufacturer’s
information on recommended bend radii is
not available, the following radii may be considered suitable

2.14.1.2.

Unarmoured sheathed cables 6 times the cable diameter

2.14.1.3.

Armoured sheathed cables 12 times the cable diameter

2.14.1.4.

(C

2.15.

Wire jumpers on devices shall be run within the loom, so as to not be
misplaced on device replacement.

3.

Cable Colors and type:

Where possible the DKI standards for cable colors are to be strictly followed

3.1.

Power cables

110v

240v Orange

3.2.

Instrument cables

0v

24v
Black

3.3.

IS cables -



Blue

3.4.

Flexible cables and cords shall be 1kV or 450/750V rated, heavy duty, with
multiple stranded tinned copper conductors of minimum cross section and
with a tinned copper braided screen.

3.5.

Insulation materials may be either PVC, EPR or NBR

3.6.

Screens shall be included in all Zone 1 cables , with the exception of
short lengths (not > 600mm) of instrument cables

3.7.

Wire and cable type used shall be as stated on DKI drawings, alternatives
shall be submitted for DKI approved.

3.8.

Cables used for the transmission of signals from temperature, pressure,
speed, flow, weight, level and similar signals , or any 4-20mA, 0-20mA,
24VDC or similar extra low voltage signal shall comprise twisted screened
pairs.

3.9.

Wire and cable sizes to be as stated or agreed by DKI cable block diagram
and cable schedule, alternatives shall be submitted for DKI approved.

4.

Wire Colors inside of Exe, Exd boxes and junction boxes shall be:

240v Active







Red

White

Brown

Black

Light Blue

Yellow /
green


Yellow /
green


Grey


Brown


Orange


Blue

240v Neutral

240v Earth

All earth bonding

+24vdc

24 OV

+12vdc

12 OV

4.1.

In extreme cases where use of different cores color is unavoidable, then
heatshrink sleeving applied to the cores is required.

5.

Wire segregation:-

5.1.

Segregation of wiring with differing voltage rated Insulation . Dekoron
110vac and Power/control 1kv is a mandatory requirement..

5.2.

The minimum separation distance between such cables or their related
equipment shall not be less than the distances given in the following
table:

Circuit rating

(kVA)

<1

>1 <2

>2 <5

>5

Unshielded

power cables

(mm)

300

450

600

1500

Shielded

power cables

(mm)

25

50

150

300

Separation between Power and Signal/Data Cables

5.3.

Intrinsically Safe cables may only run together with non . cables provided
that either the Intrinsically Safe cables or the . cables are armoured.

5.4.

Where a non-armoured intrinsically safe cable is installed with non
armoured power and control cables, a segregation distance of
50mm
minimum
must be strictly observed throughout the complete cable run, and within
any switchboard, junction box and the like.

6.

Wire Marking:-

6.1.

All wires regardless of location shall be plainly and suitably identified
with DKI approved, wire markers on both ends of the conductor, as per DKI
wiring diagrams.

6.2.

Each end of the wire shall have the same identifying marker . RTD+1,
OUT#46 AC, ESS-A, and etc (Refer Appendix 1). Do
not
label the cable cores
according to cable colour
nor
according to the terminal that the wire is
connected to.

6.3.

Labeling on both ends of a cable/core
must
be identical. If possible, it
should be consistent throughout the circuit.

6.4.

In addition to numbering, all cables carrying Intrinsically Safe circuits
shall be identified by a 200mm length of BLUE heat shrink material at each
termination . at every cable glanding point).

7.

Pulling Compound:-

7.1.

Pulling Compound, if used, shall be non- conductive or non-odorous.

8.

Conduit-Rigid:-

8.1.

Conduit shall be Steel Galvanised and conform to AS/NZS in conjunction
with AS/NZS or IEC directives

8.2.

Conduit bends shall have suitable bend radii for the number of wires being
carried.

8.3.

Conduit shall have no more than 40% fill ratio for new installations.

8.4.

Conduit Elbows and Tees shall be Steel and of the inspection type.

开放英语-seaport


开放英语-seaport


开放英语-seaport


开放英语-seaport


开放英语-seaport


开放英语-seaport


开放英语-seaport


开放英语-seaport



本文更新与2021-01-20 07:13,由作者提供,不代表本网站立场,转载请注明出处:https://www.bjmy2z.cn/gaokao/537280.html

电气接线标准的相关文章

  • 余华爱情经典语录,余华爱情句子

    余华的经典语录——余华《第七天》40、我不怕死,一点都不怕,只怕再也不能看见你——余华《第七天》4可是我再也没遇到一个像福贵这样令我难忘的人了,对自己的经历如此清楚,

    语文
  • 心情低落的图片压抑,心情低落的图片发朋友圈

    心情压抑的图片(心太累没人理解的说说带图片)1、有时候很想找个人倾诉一下,却又不知从何说起,最终是什么也不说,只想快点睡过去,告诉自己,明天就好了。有时候,突然会觉得

    语文
  • 经典古训100句图片大全,古训名言警句

    古代经典励志名言100句译:好的药物味苦但对治病有利;忠言劝诫的话听起来不顺耳却对人的行为有利。3良言一句三冬暖,恶语伤人六月寒。喷泉的高度不会超过它的源头;一个人的事

    语文
  • 关于青春奋斗的名人名言鲁迅,关于青年奋斗的名言鲁迅

    鲁迅名言名句大全励志1、世上本没有路,走的人多了自然便成了路。下面是我整理的鲁迅先生的名言名句大全,希望对你有所帮助!当生存时,还是将遭践踏,将遭删刈,直至于死亡而

    语文
  • 三国群英单机版手游礼包码,三国群英手机单机版攻略

    三国群英传7五神兽洞有什么用那是多一个武将技能。青龙飞升召唤出东方的守护兽,神兽之一的青龙。玄武怒流召唤出北方的守护兽,神兽之一的玄武。白虎傲啸召唤出西方的守护兽,

    语文
  • 不收费的情感挽回专家电话,情感挽回免费咨询

    免费的情感挽回机构(揭秘情感挽回机构骗局)1、牛牛(化名)向上海市公安局金山分局报案,称自己为了挽回与女友的感情,被一家名为“实花教育咨询”的情感咨询机构诈骗4万余元。

    语文